Comparison between Doble F6150 and Omicron CMC 356
Introduction : Doble F6150 and Omicron CMC 356
Several people do ask what their best protective relay test-set really is; they have difficulties in deciding what protective relay is best for their organization or business. However, deciding on the best test-set for you should at least involve some research, but do not worry, we’ve took it upon ourselves at kaaraba.com to compare and contrast and also show you the demonstration from the protective relay test-set vendors, so that you can choose which one fits your organization’s needs and relay testers’ requirements.
This post discusses and aimed at showing the comparison and or contrasting features of the Doble F6150 and Omicron CMC 356, which we hope will help you make an informed decision.
Protection Relay Test-Set Current Amplifiers
Below is a quick outline of the current amplifier specifications of the Doble F6150 and Omicron CMC 356 from the major test-set manufacturers’ specification sheets, they are arranged in alphabetical order:
| Doble F6150SV | Omicron CMC 356 | |
| 3-Phase Max Current | 35 A (70 A*) | 64 A |
| 3-Phase Max VA | 75 VA (262.5 VA*) | 860 VA |
| 3-Phase Current (V) | 50 V rms | |
| 6-Phase Max Current | 17.5 A (35 A*) | 32 A |
| 6-Phase Max VA | 87.5 VA (131.25 VA*) | 430 VA |
| 6-Phase Max Current (V) | 35 V peak | |
| 1-Phase Max Current | 105 A (210 A*) | 128 A |
| 1-Phase Max VA | 525 VA (787.5 VA*) | 1740 VA |
| 1-Phase Max Current (V) | 140 V Peak |
Current Amplifier Magnitude
Although both the Doble F6150 and Omicron CMC 356 generate approximately the same amount of current, the Omicron is proven to be able to generate that current for a long period of time. However, this should not be something of great concern during standard protection relay testing because ideally, a protective relays should be able operate faster at higher currents. Meanwhile, if under any circumstances you need more current than what is shown in the specifications, it is very simple because all of the manufacturers have amplifier units which they can use to generate additional current channels if need be.
Current Amplifier Compliance Voltage
According to the specification, the CMC 356 (single-phase) specifications is higher, so because of this specification there are a number of relays that the CMC 356 will be able to test which the Doble F6150 cannot test.
When taking a critical look, The Doble F6150 does not list the compliance voltage in its specification; however, we can equally guess that it is lower than the CMC 356 due to the fact that the VA is drastically lower. The Doble F6150 has convertible voltage channels, so in this case, assuming one of the relays you want to test requires more than 99Vrms or 140Vpeak, then you may want to give the Doble some bonus points, in as much as test requires less than 9.0A, and you are prepared to change leads frequently between tests on other, most likely more common, relays.
Reliability and Customer Support
Customer support and Hardware reliability can be extremely important issues that can be somehow difficult to judge or evaluate until you are a customer. It is proven beyond reasonable doubt that the CMC 356 happens to be the most reliable test-set, and as well given additional points on the reliability front.
Protection Relay Test-Set Voltage Amplifiers
The main voltage amplifier specifications are listed below:
| Doble F6150SV | Omicron CMC 356 | |
| 4-Phase Max Voltage | 300 V* | 300 V |
| 4-Phase Max VA | 75 VA | 75 VA |
| 1-Phase Max Voltage | 600 V | 600 V |
| 1-Phase Max VA | 300 VA | 275 VA |
| DC Voltage | 6 – 300VDC | 0 – 264 VDC |
| DC Voltage Watts | 90 W | 50 W |
* 6-voltage channels are available
What do these specifications really mean?
Obviously, Doble F6150 and Omicron CMC 356 can provide a power supply for a relay, and also supply three-phase voltages up to the specifications we have listed above. The Doble F6150 is capable of powering a relay and also supplies six voltages concurrently, while the CMC 356 can power the relay with four dedicated voltages respectively. Both test-sets can test six-phase voltage balance relays; however, the Omicron CMC 356 requires some complicated wiring connections in order to do this.
Why You Should Hire Our Products at www.kaaraba.com
You can take advantage of Kaaraba.Com expert advice so that you can get the best, and the most appropriate plus lucrative equipment for the job. We supply a lot of industries, and as well save you save your time and money by passing on the benefit of our experience for free. We give you honest advice in order to make the most informed decisions; it is just a phone call away.
If on a rare occasion we don’t have a particular product you are looking for, rather than hiring you something that is not capable of doing the job, we would rather direct you to the best alternative supplier; this shows that at kaaraba.com, we are not just after hiring our products to you, we are also committed to your providing the best for your business.
No cause for alarm as you will always be provided with full instructions, and if you still need more help, call our technical team on (+44) 7397 948666 . Our aim is to save you money, time, and frustration. We present the top quality equipment from major manufacturers.
At kaaraba.com you’ll get the most reliable, accurate, and well maintained equipments available. Our prices are frequently reviewed in order to make sure you always enjoy the best value for your money.
We have made a significant investment in test equipment so we ensure that it’s well packed to minimize damage and delay. We really do listen to you. You won’t waste your time contacting us at kaaraba.
Every request for equipment is carefully considered and logged. Listening to our clients helps us keep our product range relevant and up to date. However, if you are unhappy or disappointed about any aspect of our service please let us know so we that can put it right.
Reliserv solution relay service providers and dealers are designed to guarantee continuity of services. Relay test kit omicron characteristic is to take a look at the relays and notice unwanted conditions for you to motive harm to assets and existence.